PERFORMANCE OF A DIRECT EVAPORATIVE COOLER OPERATING IN KHANDESH REGION IN MAHARASHTRA
##plugins.themes.academic_pro.article.main##
Abstract
The present work analyze the performance of a direct evaporative cooler in Khandesh region in Maharashtra. The experimental study is based on weather data from Khandesh region in Maharashtra. In this region in summer temperature and humidity in the range of 37 to 48 C and 40% to 70% respectively and in rainy season relative humidity reaches to more than 90%.The direct evaporative cooler consists of a aspen pads are mostly used.The performance of the evaporative cooler is evaluated using the output temperature, saturation efficiency.The output temperature of the air varies between 27.8°C and 26°C, while the cooling capacity is between 1.84 kW and 2.56 kW.